Vue de la page 94
VCC-X Controller Technical Guide
APPENDIX D - VCC-X BACnet
®
95
VFD Test Screens
Refer to the following map when navigating through the VFD Test
Screens. VFD test screens are only used when VFD is connected
via MODBUS communications. From the VFD TEST Screen, press
<ENTER> to scroll through the screens.
VFD TEST
ENABLED/
DISABLED
VFD COMPRESSOR TEST
Values are Enable or Disabled.
VFD FREQ
0.0 HZ
VFD COMPRESSOR FREQUENCY
Current VFD Frequency. Values are 0.0 HZ to
VFD VOLT
0.0
VFD COMPRESSOR VOLTAGE
Current VFD Voltage.
VFD AMPS
0
VFD COMPRESSOR AMPS
Current VFD Amps.
Address Screen
ADDRESS
1(152)
CURRENT BOARD ADDRESS
Con gure the address according to which refrigerant circuit
this module represents—1=A, 2=B, 3=C, 4=D.
Number in parentheses is E-BUS address.
VFD Test Screens & Address Screen