VCC-X Controller Technical Guide
VCC-X CONTROLLER WIRING
25
GND
TMP
OE210, OE211, OE212, OE213
Space Temperature Sensor
OVR
R
E
L
O
C
R
E
M
R
O
A
W
AUX
Wire Required For
Sensors With Slide
Adjust Option Only
AI1
AI2
GND
VCC-X Controller
Space Temperature Sensor
The OE210, OE211, OE212, OE213 Space Temperature Sensor
is typically used for constant volume HVAC unit applications
controlling one zone. The Space Temperature Sensor is a 10K Type
III thermistor sensor and should be mounted approximately 5 feet
above the oor in the space that is to be controlled.
Figure 11: OE210, OE211, OE212, OE213 – Space Temperature Sensor Wiring and Slide Adjust
Space Temperature Sensor Wiring
The Space Temperature Sensor is available as a sensor only, sensor
with override button, sensor with slide adjust, and sensor with slide
adjust and override con gurations.
See Figure 11 below for complete Space Temperature Sensor wiring
details.