VCC-X Controller Technical Guide
VCC-X CONTROLLER WIRING
21
VCC-X Controller Output Wiring
Figure 7: VCC-X Controller Output Wiring
NOTE:
ALL RELAY OUTPUTS ARE NORMALLY
OPEN AND RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD
CONFIGURABLE RELAY OUTPUT #5
CONFIGURABLE RELAY OUTPUT #4
CONFIGURABLE RELAY OUTPUT #3
CONFIGURABLE RELAY OUTPUT #2
24 VAC POWER
SUPPLY FAN
24 VAC ONLY
R1
G
R4
R5
R3
R2
HVAC UNIT CONNECTIONS
R
COMM
CONFIGURABLE RELAY OUTPUT #6
R6
AOUT1
AOUT2
AOUT3
GND
GND
24VAC
GND
VCC-X CONTROLLER
Line
Voltage
Size Transformer For
Correct Total Load.
VCC-X Controller = 15 VA
R7
R8
CONFIGURABLE RELAY OUTPUT #7
CONFIGURABLE RELAY OUTPUT #8
AOUT4
ECONOMIZER
ACTUATOR
SUPPLY FAN VFD
+
COM
2+
Y13
COM1
MODULATING HEATING
(SCR OR HOT WATER VALVE)
+
COM
EXHAUST FAN VFD
+
COM
SHIELD
SHIELD
5
Economizer Feedback
NOTE: RELAY CONTACTS R2-R8 MAY BE CONFIGURED FOR:
1.) COOLING STAGES
2.) HEATING STAGES
4.) EMERGENCY HEAT
5.) MOD HEAT ENABLE
6.) MOD COOL ENABLE
7.) MORNING WARM-UP
9.)
11.) LOW AMBIENT
12.) EXHAUST
13.)
ECONOMIZER
14.)
15.) OCCUPIED
16.) OVERRIDE
10.) PREHEAT
3.) AUX HEAT
17.) ALARM
REHEAT
HEAT WHEEL
8.) MORNING COOL-DOWN
VCC-X Controller Outputs
The VCC-X Controller must be connected to 24 VAC as shown
in the wiring diagram below. Please see Table 1 for correct VA
requirements to use when sizing the transformer(s) used for powering
the Controller.
Also please note that when wiring the VCC-X Controller, its contacts
must be wired as wet contacts (connected to 24 VAC).