VAV/ZONE CONTROLLER PROGRAMMING
VCM-X / RNE Operator Interfaces Technical Guide
61
VAV/Zone Setpoint Screens
Setpoint Screen #6 - Damper Air ow Max &
Vent Min
XX Box Spts IDXXXX
Damper/Airflow Spt
Maximum..: XXX %
Vent Min.: XXX %
The VAV/Zone Controller will not allow the damper or air ow calcula-
tion to exceed the Maximum setpoint while it is allowing the damper to
modulate. During Vent mode when there is no heating or cooling demand,
the damper or air ow will maintain at least the Vent Min amount of
air ow into the zone for ventilation.
Description Minimum Default Maximum
Maximum 0% or 0 CFM 100% or
1000 CFM
100% or
30000 CFM
Vent Min 0% or 0 CFM 25% or
250 CFM
100% or
30000 CFM
Setpoint Screen #7 - Damper Air ow Cool/
Heat Minimum
XX Box Spts IDXXXX
Damper/Airflow Spt
Cool Min.: XXX %
Heat Min.: XXX %
During Supply Air Cooling Mode, if the space being served by this
damper is satis ed and has no cooling demand, the damper will close to
this Cool Min setting. This provides a minimum amount of air ow into
the space for ventilation, even if the space does not require additional
cooling. During Supply Air Heating Mode, if the space being served
by this damper is satis ed and has no heating demand, the damper will
close to this Heat Min setting. This provides a minimum amount of
air ow into the space for ventilation, even if the space does not require
additional heating.
Description Minimum Default Maximum
Cool Min 0% or
0 CFM
10% or
1000 CFM
100% or
30000 CFM
Heat Min 0% or
0 CFM
10% or
100 CFM
100% or
30000 CFM
Setpoint Screen #8 - Damper Air ow Night Min
and Fan On Min
XX Box Spts IDXXXX
Damper/Airflow Spt
Night Min.: XXX %
Fan On Min.: XXX %
The Night Min is the position the damper will move to when the sys-
tem is in Override Mode and this particular damper is not part of the
override group. This Night Min position only affects non-fan powered
boxes. The Fan On Min is the minimum damper or air ow setting used
to activate the parallel fan if installed. Pressure Independent = CFM.
Pressure Dependent = %.
Description Minimum Default Maximum
Night Min 0% or
0 CFM
0% or
0 CFM
100% or
9999 CFM
Fan On Min 0% or
0 CFM
25% or
250 CFM
100% or
9999 CFM
Setpoint Screen #9 - Damper Air ow Reheat Min
XX Box Spts IDXXXX
Damper/Airflow Spt
Reheat Min.: XXX %
The Reheat Min is the damper or air ow setting used during the Space
Reheat Mode of operation.
Description Minimum Default Maximum
Reheat Min 0% or
0 CFM
0% or
0 CFM
100% or
30000 CFM
Setpoint Screen #10 - Damper Air ow Fixed
Position
XX Box Spts IDXXXX
Damper/Airflow Spt
Fixed Pos: XXX %
Many times while troubleshooting a system, it is useful to have the zone
damper set to a speci c damper position or air ow setting. This setpoint
can be used to determine where the damper/air ow will remain when the
VAV/Zone Controller receives a Force to Fixed Position command.
Description Minimum Default Maximum
Fixed Pos 0% or
0 CFM
0% or
0 CFM
100% or
9999 CFM