Orion-system VCM-X/RNE Operator Interfaces Manuel d'utilisateur Page 25

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 84
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 24
VCM-X / RNE Operator Interfaces Technical Guide
VCM-X CONFIGURATION
25
VCM-X Con guration Screens
Con guration Screen #39 - Emergency
Shutdown Input
VCM-X Cnfg ID 59
Emergency Shutdown
Input: NO
[0=NO 1=YES]
Enter <1> for YES if a Smoke Detector/Firestat or other Emergency
Shutdown input is connected to the binary input. If the Emergency
Shutdown input is active, the Supply Fan, Heating and Cooling Relay
Outputs will be disabled. Enter <0> for NO. Default is NO.
Con guration Screen #40 - Return Air Bypass
Control
VCM-X Cnfg ID 59
Return Air Bypass Con-
trol: NO
[0=NO 1=YES]
Enter <1> for YES if your HVAC unit requires Return Air Bypass
Control for Dehumidi cation Reheat. Enter <0> for NO. Default is NO.
Con guration Screen #41 - Broadcast OA Temp
VCM-X Cnfg ID 59
Broadcast Outdoor
Temperature: NO
[0=NO 1=YES]
The VCM-X can broadcast its Outdoor Air Temperature Reading to
other HVAC units if they are not equipped with their own Outdoor Air
Temperature sensors. A network communications device is needed in
order for this feature to operate. Enter
<1> for YES - Broadcast Outdoor
Temperature. Enter <0> for NO. Default is NO.
Con guration Screen #42 - Broadcast OA Humidity
VCM-X Cnfg ID 59
Broadcast Outdoor
Humidity: NO
[0=NO 1=YES]
The VCM-X can broadcast its Outdoor Air Humidity reading to other
HVAC units if they are not equipped with their own Outdoor Air Hu-
midity sensors. A network communications device is required in order
for this feature to operate. Enter
<1> for YES - Broadcast Outdoor
Humidity. Enter <0> for NO. Default is NO.
Con guration Screen #43 - Broadcast Supply
Temperature
VCM-X Cnfg ID 59
Broadcast Supply
Temperature: YES
[0=NO 1=YES]
This broadcast sends the VCM-X’s Supply Air Temperature to all con-
trollers on its local loop. This broadcast needs to be con gured on a VAV
or Zoning System using the VCM-X with Orion VAV/Zone Controllers.
A network communications device is required in order for this feature
to operate. Enter
<1> for YES or <0> to NO. Default is NO.
Con guration Screen #44 - Broadcast Status
Fan & Heat
VCM-X Cnfg ID 59
Broadcast Status
Fan & Heat: NO
[0=NO 1=YES]
This broadcast sends the VCM-X’s Supply Fan and Heating Status to
all controllers on its local loop. This broadcast needs to be con gured
on a VAV or Zoning System using the VCM-X with Orion VAV/Zone
Controllers. A network communications device is required in order for
this feature to operate. Enter
<1> for YES or <0> for NO. Default is NO.
Con guration Screen #45 - Broadcast Internal
Time Clock
VCM-X Cnfg ID 59
Broadcast Internal
Time Clock: NO
[0=NO 1=YES]
This broadcast sends the time from the VCM-X’s Internal Time Clock
to all controllers on its local loop. This broadcast needs to be con gured
on a VAV or Zoning System using the VCM-X with Orion VAV/Zone
controllers. A network communications device is required in order for
this feature to operate, but can also be used to synchronize all controllers
on the local loop. Enter
<1> for YES or <0> for NO. Default is NO.
Vue de la page 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 83 84

Commentaires sur ces manuels

Pas de commentaire