Orion-system VCC-X Controller Manuel d'utilisateur Page 58

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 96
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 57
Zone
Zone
VCC-X STATUS
VCC-X Operator Interface SD
58
VCC-X Status Screens
Status Screen #14 - PREHEAT-X Controller
Current Leaving Air and Entering Air
Temperature
VCC-X v1.02 ID #
Preheat-X Temps
Leaving Air: 0.0ºF
Entring Air: 0.0ºF
Line 3 Current PREHEAT-X Leaving Air Temperature
If the Preheat-X Controller (and the associated Leaving
Air Temperature Sensors) is installed and con gured,
this line will display the current Preheat-X Leaving Air
Temperature.
Line 4 Current PREHEAT-X Entering Air Temperature
If the Preheat-X Controller (and the associated Entering
Air Temperature Sensor) is installed and con gured, this
line will display the current Preheat-X Entering Air
Temperature.
Status Screen #15 - PREHEAT-X Controller
Modulating Position and Active Stages
VCC-X v1.02 ID #
Preheat-X Status
Mod Pos: XXX%
Active Stages: X
Line 3 Current PREHEAT-X Modulating Position
If you have a PREHEAT-X Controller connected to
the VCC-X Controller and are using Modulating Heat,
this is the current modulating heat signal
.
Line 4 Current PREHEAT-X Active Stages
If you have a PREHEAT-X Controller connected to the
VCC-X Controller, and are using staged heat, this is the
number of stages currently active.
Status Screen #16 - OA Drybulb and Humidity
VCC-X v1.02 ID #
Outdoor Conditions
Drybulb: 0.0ºF
Humidity: XXX%
Line 3 Current Outdoor Air Drybulb
If an E-BUS Outdoor Air Temperature/Humidity Sensor
has been installed and con gured on the VCC-X, the
current Outdoor Air Temperature will display on this
line. If the sensor fails, this line will display a
temperature that is half way between the Cooling and
Heating Lockout Setpoints.
Line 4 Current Outdoor Air Relative Humidity
If an E-BUS Outdoor Air Temperature/Humidity Sensor
has been installed and con gured on the VCC-X, the
Outdoor Air Relative Humidity Percentage will appear
on this line. If not, this line will display 0%.
Status Screen #17 - OA Wetbulb and Dewpoint
VCC-X v1.02 ID #
Outdoor Conditions
Wetbulb: 0.0ºF
Dewpoint: 0.0ºF
Line 3 Current Wetbulb Temperature
If an E-BUS Outdoor Air Temperature/Humidity Sensor
has been installed and con gured on the unit, this line
will display the calculated Outdoor Air Wetbulb
Temperature. If not, it will display 0°F.
Line 4 Current Calculated Outdoor Air Dewpoint
Temperature
If an E-BUS Outdoor Air Temperature/Humidity Sensor
has been installed and con gured on the unit, the
calculated Outdoor Air Dewpoint Temperature will
appear on this line. If not, this screen displays 0°F.
Vue de la page 57