VCC-X Operator Interface SD
VCC-X CONFIGURATION
25
Con guration Screens
In order to correctly set up the VCC-X Controller, you must rst
con gure several parameters in regard to the type of HVAC unit
and system you have installed. Most of these values and operat-
ing parameters are only set once at the initial system setup and are
never changed.
Modular Service Tool Instructions
No matter what screen or menu you’re in, press <CONFIGURA-
TION>. The Unit Selection Screen will appear, shown below, request-
ing that you enter the unit ID number.
VCC-X CONFIGURATION
RSM CONFIGURATION
Select & Press Enter
Enter the correct unit ID number of the VCC-X Controller you want
to con gure and then press
<ENTER>. Once communication is es-
tablished, the *00* message will go away. Then
press <>. Select
VCC-X Con guration and then press <ENTER>. Press <ENTER>
to save entered data and press <> to scroll through the screens.
NOTE: If the *00* remains, it indicates a communication
failure to the controller.
System Manager SD Instructions
From any Main screen, press <SETPOINTS>. The screen below
will appear because this option requires passcode clearance. Only a
Level 2 passcode can change setpoints.
THIS ACTION REQUIRES
PASSCODE CLEARANCE
Enter Passcode: XXXX
If the correct passcode was entered, the Unit Selection Screen will
be displayed.
Enter Unit Address
Then Press Enter
Selected Unit #_1
Press Down
Enter the correct unit ID number of the VCC-X Controller you
want to con gure and then press <ENTER>. Once communication
is established, the *00* message will go away. Then
press <>.
NOTE: If the *00* remains, it indicates a communication
failure to the controller.
The following screen will be displayed:
Change Setpoints
Configure Unit
Save/Copy/Restore
VCC-X CONFIGURATION
RSM CONFIGURATION
Select & Press Enter
On the rst screen, scroll down to the ‘Con gure Unit’ option and
press <ENTER>. On the second screen, select VCC-X Con guration
and then press
<ENTER>. This will take you to the rst Con gura-
tion Screen shown below.
Con guration Screen #1 - Sensor Scaling
VCC-X Cnfg ID #
Sensor Scaling
Fahrenheit
USE < or > TO CHANGE
Options are Fahrenheit or Celsius. If you make a change to this
screen, after you press <ENTER> to have the system accept the
change, you must return to the Unit Selection Screen to re-establish
communications with the Controller. Default is Fahrenheit.
Con guration Screen #2 - RSM #1 & #2
Module Installed
VCC-X Cnfg ID #
RSM#1 Installed: NO
RSM#2 Installed: NO
USE < or > TO CHANGE
If you have a one RSMV Module installed, the 1st con guration op-
tion should be con gured as YES. If you have a 2nd RSMV Module
installed, the 2nd con guration option should be con gured as YES.
Default is NO.
VCC-X Con guration Screens
Enter Unit Address
Then Press Enter
Selected Unit #_1
Press Down