Section 4: Con guring Analog Inputs
GPC-XP Controller Technical Guide
14
Sensor Reading, Scaling, and Override Duration
Sensor Reading Appendix
Select from the drop down list in the <Sensor Reading Appen-
dix>
eld (Figure 12 below) to give the sensor reading a quali er.
For User De ned, type in your own quali er in the < User De ned
Appendix>
eld.
User De ned: Enter your own in the
User De ned Appendix eld
°F: Fahrenheit
°C: Celsius
PPM: Parts Per Million
PSI: Pound per Square Inch
“WG: Inches of Water Gauge
Ft.: Feet
RPM: Revolutions per Minute
RH%: Humidity Percentage
%: Percentage
VDC: Volts D.C.
BTU: British Thermal Unit
CFM: Cubic Feet per Minute
HR: Hours
MIN: Minutes
GPM: Gallons per Minute
Sensor Scaling
Figure 12: Sensor Reading Appendix Field
Figure 13: Sensor Scaling Field
All readings are user-scalable according to the number of digits
to the right of the decimal point. See Figure 13 and values and
examples below.
X 1 65°F
X 10 65.5°F
X 100 65.54°F
X 1000 65.543°F
Internal Schedule Used for Night Setbacks
and Overrides
If this input is reading a temperature sensor which will be using Night
Setbacks or Unoccupied Overrides, select the applicable schedule.
See Figure 14 below. Actual Schedules are set in the Schedules
Window. See instructions on page 35 for setting Schedules.
Type a value between
.1 Hours and 24 Hours
and press <ENTER>
to save.
Figure 15: Override Duration Field
Override Duration
When setting an Override Duration, you must rst select the schedule
in the <Internal Schedule Used for Night Setbacks & Over-
rides>
eld. When either a WattMaster Thermistor Temperature
Sensor or a Communicating Temperature Sensor is used, an Over-
ride Duration can be entered. When the Override Button is pushed
on one of these sensors during the scheduled Unoccupied Mode,
the schedule will be overridden back into the Occupied Mode. The
Override Duration determines the amount of time the schedule will
remain in Override Occupied Mode.
NOTE: If using a Thermistor Sensor, the Override can be
cancelled by pressing the override button for 3 to 10
seconds. If using a Communicating Sensor with an
Override button, pressing the button while in Override
operation will cancel the Override.
Figure 14: Schedule for Night Setbacks and
Overrides