MODGAS-XWR Technical Guide
OVERVIEW
3
General Information
YS102530 REV 1
GAS VALVE 2
GAS VALVE 1
PO-IGN2
PO-IGN1
COMMON
RLY4
RLY3
RLY2
RLY1
WATTMASTER
CONTROLS
MADE IN USA
AUX BIN
HEAT EN
RESET IN
OPTIONS
SAT
GND
AUX AIN
GND
STATUS
ALARM
COMM
POWER
ANODE
ANODE
ANODE
M
ENTER
UP
DOWN
ALARM
MENU
OE377-26-00060
MODGAS-XWR
AAON No.: V20780
WattMaster No:
#SW000055
Rev.: 1A
E-BUS
CONNECT
I2C
CONNECT
+24 VAC
GND
CONTACT RATING
IS 1 AMP MAX
@ 24 VAC
HEAT 1
LOW SPEED
FAN
PROOF OF IGNITION 1
PROOF OF IGNITION 2
GAS VALVE 2
GAS VALVE 1
GAS VALVE
TERMINALS
HEAT 2
COMMON
RELAY OUTPUT
TERMINALS
INPUT TERMINALS (TYPE)
HEAT ENABLE (BI)
AUX. (BI)
GND
RESET INPUT (AI)
SAT INPUT (AI)
GND(AI)
GND
AUX. (AI)
www.aaon.com
MODGAS-XWR CONTROLLER
(OE377-26-00060)
Figure 1: OE377-26-00060 MODGAS-XWR Controller
Features
The MODGAS-XWR Controller provides the following:
Can control two (2) Gas Valves using input from
Proof of Ignition Modules
Up to four (4) MODGAS-XWR Modules can be daisy-
chained together to control up to eight (8) Modulation Gas
Valves
Monitors Supply Air Temperature and Supply Air Reset
and modulates gas valves to maintain Setpoint
Provides active relays to control the Fan and
Heat Stages
Contains a 2 x 8 LCD character display and 4 buttons
that allow for status display, setpoint changes, and
con guration changes
NOTE: The MODGAS-XWR Controller contains no user-
serviceable parts. Contact quali ed technical personnel
if your MODGAS-XWR Controller is not operating
correctly.
Overview
The OE377-26-00060 MODGAS-XWR Controller (AAON Part No.
V20780) is designed to modulate up to two (2) gas valves to maintain
a desired Discharge Air Temperature. The MODGAS-XWR Control-
ler also controls the speed of the induced draft fan to maintain proper
combustion in the heat exchanger. See Figure 1.
The controller can be used as a stand-alone unit or be connected to
a VCM-X E-BUS Controller (OE332-23E-VCMX; AAON Part No.
V07150), VCB-X Controller (OE335-26B-VCBX; AAON Part No.
V28940), VCC-X Controller (OE338-26B-VCCX; AAON Part No.
V42430), or 12 Relay E-BUS Expansion Module (OE358-23E-12R;
AAON Part No. R69180) using a modular cable.
The MODGAS-XWR Controller can be con gured at the factory for one
(1) modulating valve, two (2) staged modulating valves, or one (1) modu-
lating with multiple xed staged valves (stand-alone operation only).
When using the MODGAS-XWR Controller to replace an existing
MODGAS II Controller, see Appendix B, page 27 for details.