VCM - Operator InterfacesTechnical GuideVCM Controller Code: SS1016Requires System Manager Code: SS1010 Version 3.0 and upRequires Service Tool Code:
Technical GuideOperator Interfaces10System Manager Override SearchWhen a space sensor with override option is used with any VAV/Zonecontroller or VCM
Operator Interfaces Technical Guide11Modular Service Tool Initialization ScreenAfter connecting the Service Tool to the controller with the suppliedc
Technical GuideOperator Interfaces12Modular Service Tool Override SearchWhen a space sensor with override option is used with any VAV/Zonecontroller
Operator Interfaces Technical Guide13Programming The VCM ControllerApplication ConfigurationsThis area of the manual is designed to simplify the progr
Technical GuideOperator Interfaces14Screen #26 = “0” or “1”Configure the proper Building Pressure Output Signal.Screen #28 = “YES”Only if a Smoke Det
Operator Interfaces Technical Guide15Screens #42-#61Refer to the AAON® wiring diagram inside the unit beforeconfiguring onboard and expansion board re
Technical GuideOperator Interfaces16Programming The VCM ControllerConfiguration Screen IndexThe available Configuration Screens for the VCM controlle
Operator Interfaces Technical Guide17Configuration ScreensIn order to correctly setup the VCM controller you must first configureseveral parameters in
Technical GuideOperator Interfaces18Programming The VCM ControllerConfiguration Screen #5VCM Cnfg ID 59HVAC Reset SourceLoop Rate: 10 s[1-255 Seconds
Operator Interfaces Technical Guide19Configuration Screen #14VCM Cnfg ID 59Mod Cooling: NOMod Heating: NO[0=NO 1=YES]Enter a “1” for “YES” if the HVAC
Table Of ContentsIntroduction ...
Technical GuideOperator Interfaces20Programming The VCM ControllerConfiguration Screen #22VCM Cnfg ID 59CO2 SensorOutput Signal: 0[0=None 1=mA 2=VDC]
Operator Interfaces Technical Guide21Configuration Screen #31VCM Cnfg ID 59Broadcast OutdoorTemperature: NO[0=NO 1=YES]The VCM can broadcast its Outd
Technical GuideOperator Interfaces22Configuration Screen #39VCM Cnfg ID 59Enable Broadcast ToMultiple Loops: NO[0=NO 1=YES]When “1=YES” is selected,
Operator Interfaces Technical Guide23Setpoint Screen #13 Economizer Setpoints OAT/WB EnableSetpoint Screen #14 Economizer Setpoints Min Position &
Technical GuideOperator Interfaces24Programming The VCM ControllerSetpoint Screen #2VCM Spts ID 59HVAC Mode SelectDeadband: 1.0°FThis Setpoint is ad
Operator Interfaces Technical Guide25Setpoint Screen #8VCM Spts ID 59Cutoff Temperature Lo SAT: 40°F Hi SAT: 150°FThe VCM controller will tempor
Technical GuideOperator Interfaces26Setpoint Screen #10 VCM Spts ID 59 Morning Warm Up Target Temp: 70°FMax Length..: 60 MinWhen the VCM is conf
Operator Interfaces Technical Guide27Setpoint Screen #16VCM Spts ID 59CO2 Protection LimitMax Level..: 900 PPMReset Rnge.: 100 PPMWhen the CO2 level r
Technical GuideOperator Interfaces28Setpoint Screen #18 VCM Spts ID 59Building PressureSetpoint: 0.02”Deadband: 0.01”Direct Acting ControlIf an Exhau
Operator Interfaces Technical Guide29Setpoint Screen #22VCM Spts ID 59Low OA AmbientProtectionTemperature: 30°FFor cold climates where freezing temper
Operator Interfaces 3 Technical GuideModular System ManagerENTERCLEARESCPREVNEXTDOWNUP654DEC7081329MINUS-STATUSSETPOINTSSCHEDULESALARMSOVERRIDES9.00&q
Technical GuideOperator Interfaces30Setpoint Screen #26VCM Spts ID 59Air To Air Heat PumpAuxiliary HeatingDelay: 3 MinIf your VCM is configured to op
Operator Interfaces Technical Guide31SchedulingThe VCM controller scheduling screens are accessed by pressing the“Schedule” button on either the Syst
Technical GuideOperator Interfaces32Holiday Start/Stop Times VCM Hldy ID 59 Holiday ScheduleStart Event #1: xxxxStop Event #1: xxxx VCM Hldy ID
Operator Interfaces Technical Guide33Programming Date Program Time/DateMonth (1-12): xxDay (1-31): xxYear (00-99): xxMonth Enter the Mo
Technical GuideOperator Interfaces34Programming The VCM ControllerCaution: The Damper Force Modes should only be used by quali-fied service personnel
Operator Interfaces Technical Guide35Analog Output 4 ScreenMod Heating Override Analog Output #4Override Volts: -1.0 [-1.0=Auto]Analog Output 5 S
Technical GuideOperator Interfaces36Programming The VCM ControllerStatusThe VCM controller status screens are accessed by pressing the “Sta-tus” but
Operator Interfaces Technical Guide37Status Screen 5 VCM v1.00 ID 59 H/C Demand: xx.x°F Space Tmp.: xx.x°FLine 2 Current Heating or Cooling DemandB
Technical GuideOperator Interfaces38Programming The VCM ControllerSSSSStatus Screen 9 VCM v1.00 ID 59Economizer.: xxx%OA Wetbulb.: xx.x°FCO2 Level..
Operator Interfaces Technical Guide39Reverse Acting Operation:0-10 VDC 0% = 10 VDC 100% = 0 VDC2-10 VDC 0% = 10 VDC 100% = 2 VDCIf you do not have a M
Technical GuideOperator Interfaces4Modular Service ToolWether you have a Stand Alone, Interconnected or Networked OrionControls System, the Modular S
Technical GuideOperator Interfaces40Status Screen 16-22 VCM v1.00 ID 59 Fan Relay: OFF Cool Stage 1: OFF Heat Stage 1: OFFLine 2 - Current Supp
Operator Interfaces Technical Guide41Programming The VAV/Zone ControllerConfigurationIn order to correctly setup the VAV/Zone controller you must firs
Technical GuideOperator Interfaces42Programming The VAV/Zone ControllerConfiguration Screen #7HC Box Cnfg IDxxxxProportional HeatingSignal..: 0 - 1
Operator Interfaces Technical Guide43SetpointsSetpoint Screen #1HC Box Spts IDxxxx Occupied SetpointsCooling...: xx°FHeating...: xx°FEnter t
Technical GuideOperator Interfaces44Programming The VAV/Zone ControllerSetpoint Screen #6HC Box Spts IDxxxx Damper/Airflow SptCool Min.: xxx %H
Operator Interfaces Technical Guide45Setpoint Screen #11HC Box Spts IDxxxx Day/Night Schedule Control #: x0=AHU 1-7=SchedulerThis screen allows
Technical GuideOperator Interfaces46Programming The VAV/Zone ControllerStatusStatus Screen #1HC Box v1.04 IDxxxx Occupied Mode Vent ModeBelo
Operator Interfaces Technical Guide47Status Screen #5HC Box v1.04 IDxxxxDamper FRC: xxx %Airflow : xxxx CFMDesired : xxxx CFMLine 2 Current Zone
Technical GuideOperator Interfaces48 1)Outputs Force 2)Dampers ForcePress the “2” key to access the Damper Force Modes screen. OutputsForce is not
Operator Interfaces Technical Guide49Programming The MiniLink PDConfigurationIn order to correctly setup the MiniLink PD you must first configuresever
Operator Interfaces Technical Guide5Modular System ManagerAs previously described, when you are connecting the Modular Sys-tem Manager to a Networke
Technical GuideOperator Interfaces50Programming The MiniLink PDStatusStatus Screen #1 Polling Device System Occupied Venting ModeXXX Min Left
Operator Interfaces Technical Guide51Notes:
Form: OR-OI-VCM-TGD-01A Printed in the USA November 2005All rights reserved Copyright 2005WattMaster Controls Inc. • 8500 NW Riv
Technical GuideOperator Interfaces6General Programming InformationThe Modular Service Tool or the System Manager allow the user toview any temperatur
Operator Interfaces Technical Guide7Mode Selection ButtonsButtonDescriptionModular Service Tool System ManagerSTATUSPressing this buttontakes you dire
Technical GuideOperator Interfaces8 InitializingSystem Manager vX.XX Wattmaster Controls Network ModeSystem Manager vX.XX Monday Operations 0
Operator Interfaces Technical Guide9System Manager NM & MM Mode Loop SearchWhen the System Manager is configured for Network Mode a loopsearch mus