Page 1 - Technical Guide

VCM - Operator InterfacesTechnical GuideVCM Controller Code: SS1016Requires System Manager Code: SS1010 Version 3.0 and upRequires Service Tool Code:

Page 2 - Table Of Contents

Technical GuideOperator Interfaces10System Manager Override SearchWhen a space sensor with override option is used with any VAV/Zonecontroller or VCM

Page 3 - Modular System Manager

Operator Interfaces Technical Guide11Modular Service Tool Initialization ScreenAfter connecting the Service Tool to the controller with the suppliedc

Page 4

Technical GuideOperator Interfaces12Modular Service Tool Override SearchWhen a space sensor with override option is used with any VAV/Zonecontroller

Page 5

Operator Interfaces Technical Guide13Programming The VCM ControllerApplication ConfigurationsThis area of the manual is designed to simplify the progr

Page 6

Technical GuideOperator Interfaces14Screen #26 = “0” or “1”Configure the proper Building Pressure Output Signal.Screen #28 = “YES”Only if a Smoke Det

Page 7

Operator Interfaces Technical Guide15Screens #42-#61Refer to the AAON® wiring diagram inside the unit beforeconfiguring onboard and expansion board re

Page 8

Technical GuideOperator Interfaces16Programming The VCM ControllerConfiguration Screen IndexThe available Configuration Screens for the VCM controlle

Page 9

Operator Interfaces Technical Guide17Configuration ScreensIn order to correctly setup the VCM controller you must first configureseveral parameters in

Page 10 - Modular Service Tool

Technical GuideOperator Interfaces18Programming The VCM ControllerConfiguration Screen #5VCM Cnfg ID 59HVAC Reset SourceLoop Rate: 10 s[1-255 Seconds

Page 11

Operator Interfaces Technical Guide19Configuration Screen #14VCM Cnfg ID 59Mod Cooling: NOMod Heating: NO[0=NO 1=YES]Enter a “1” for “YES” if the HVAC

Page 12

Table Of ContentsIntroduction ...

Page 13

Technical GuideOperator Interfaces20Programming The VCM ControllerConfiguration Screen #22VCM Cnfg ID 59CO2 SensorOutput Signal: 0[0=None 1=mA 2=VDC]

Page 14

Operator Interfaces Technical Guide21Configuration Screen #31VCM Cnfg ID 59Broadcast OutdoorTemperature: NO[0=NO 1=YES]The VCM can broadcast its Outd

Page 15 - Configuration Section

Technical GuideOperator Interfaces22Configuration Screen #39VCM Cnfg ID 59Enable Broadcast ToMultiple Loops: NO[0=NO 1=YES]When “1=YES” is selected,

Page 16 - Configuration Screen Index

Operator Interfaces Technical Guide23Setpoint Screen #13 Economizer Setpoints OAT/WB EnableSetpoint Screen #14 Economizer Setpoints Min Position &

Page 17 - [0=NO 1=YES]

Technical GuideOperator Interfaces24Programming The VCM ControllerSetpoint Screen #2VCM Spts ID 59HVAC Mode SelectDeadband: 1.0°FThis Setpoint is ad

Page 18

Operator Interfaces Technical Guide25Setpoint Screen #8VCM Spts ID 59Cutoff Temperature Lo SAT: 40°F Hi SAT: 150°FThe VCM controller will tempor

Page 19

Technical GuideOperator Interfaces26Setpoint Screen #10 VCM Spts ID 59 Morning Warm Up Target Temp: 70°FMax Length..: 60 MinWhen the VCM is conf

Page 20

Operator Interfaces Technical Guide27Setpoint Screen #16VCM Spts ID 59CO2 Protection LimitMax Level..: 900 PPMReset Rnge.: 100 PPMWhen the CO2 level r

Page 21

Technical GuideOperator Interfaces28Setpoint Screen #18 VCM Spts ID 59Building PressureSetpoint: 0.02”Deadband: 0.01”Direct Acting ControlIf an Exhau

Page 22 - Configuration Screen #44-68

Operator Interfaces Technical Guide29Setpoint Screen #22VCM Spts ID 59Low OA AmbientProtectionTemperature: 30°FFor cold climates where freezing temper

Page 23 - Setpoint Screen Index

Operator Interfaces 3 Technical GuideModular System ManagerENTERCLEARESCPREVNEXTDOWNUP654DEC7081329MINUS-STATUSSETPOINTSSCHEDULESALARMSOVERRIDES9.00&q

Page 24

Technical GuideOperator Interfaces30Setpoint Screen #26VCM Spts ID 59Air To Air Heat PumpAuxiliary HeatingDelay: 3 MinIf your VCM is configured to op

Page 25 - F70° F90° F

Operator Interfaces Technical Guide31SchedulingThe VCM controller scheduling screens are accessed by pressing the“Schedule” button on either the Syst

Page 26

Technical GuideOperator Interfaces32Holiday Start/Stop Times VCM Hldy ID 59 Holiday ScheduleStart Event #1: xxxxStop Event #1: xxxx VCM Hldy ID

Page 27

Operator Interfaces Technical Guide33Programming Date Program Time/DateMonth (1-12): xxDay (1-31): xxYear (00-99): xxMonth Enter the Mo

Page 28 - Setpoint Screen #21

Technical GuideOperator Interfaces34Programming The VCM ControllerCaution: The Damper Force Modes should only be used by quali-fied service personnel

Page 29 - 0° F 100° F

Operator Interfaces Technical Guide35Analog Output 4 ScreenMod Heating Override Analog Output #4Override Volts: -1.0 [-1.0=Auto]Analog Output 5 S

Page 30 - F0.0° F +100.0° F

Technical GuideOperator Interfaces36Programming The VCM ControllerStatusThe VCM controller status screens are accessed by pressing the “Sta-tus” but

Page 31 - Scheduling

Operator Interfaces Technical Guide37Status Screen 5 VCM v1.00 ID 59 H/C Demand: xx.x°F Space Tmp.: xx.x°FLine 2 Current Heating or Cooling DemandB

Page 32 - Setting Time & Date

Technical GuideOperator Interfaces38Programming The VCM ControllerSSSSStatus Screen 9 VCM v1.00 ID 59Economizer.: xxx%OA Wetbulb.: xx.x°FCO2 Level..

Page 33 - Damper Force Modes

Operator Interfaces Technical Guide39Reverse Acting Operation:0-10 VDC 0% = 10 VDC 100% = 0 VDC2-10 VDC 0% = 10 VDC 100% = 2 VDCIf you do not have a M

Page 34 - Outputs Force

Technical GuideOperator Interfaces4Modular Service ToolWether you have a Stand Alone, Interconnected or Networked OrionControls System, the Modular S

Page 35

Technical GuideOperator Interfaces40Status Screen 16-22 VCM v1.00 ID 59 Fan Relay: OFF Cool Stage 1: OFF Heat Stage 1: OFFLine 2 - Current Supp

Page 36

Operator Interfaces Technical Guide41Programming The VAV/Zone ControllerConfigurationIn order to correctly setup the VAV/Zone controller you must firs

Page 37

Technical GuideOperator Interfaces42Programming The VAV/Zone ControllerConfiguration Screen #7HC Box Cnfg IDxxxxProportional HeatingSignal..: 0 - 1

Page 38

Operator Interfaces Technical Guide43SetpointsSetpoint Screen #1HC Box Spts IDxxxx Occupied SetpointsCooling...: xx°FHeating...: xx°FEnter t

Page 39

Technical GuideOperator Interfaces44Programming The VAV/Zone ControllerSetpoint Screen #6HC Box Spts IDxxxx Damper/Airflow SptCool Min.: xxx %H

Page 40

Operator Interfaces Technical Guide45Setpoint Screen #11HC Box Spts IDxxxx Day/Night Schedule Control #: x0=AHU 1-7=SchedulerThis screen allows

Page 41 - Configuration

Technical GuideOperator Interfaces46Programming The VAV/Zone ControllerStatusStatus Screen #1HC Box v1.04 IDxxxx Occupied Mode Vent ModeBelo

Page 42

Operator Interfaces Technical Guide47Status Screen #5HC Box v1.04 IDxxxxDamper FRC: xxx %Airflow : xxxx CFMDesired : xxxx CFMLine 2 Current Zone

Page 43 - Setpoints

Technical GuideOperator Interfaces48 1)Outputs Force 2)Dampers ForcePress the “2” key to access the Damper Force Modes screen. OutputsForce is not

Page 44

Operator Interfaces Technical Guide49Programming The MiniLink PDConfigurationIn order to correctly setup the MiniLink PD you must first configuresever

Page 45

Operator Interfaces Technical Guide5Modular System ManagerAs previously described, when you are connecting the Modular Sys-tem Manager to a Networke

Page 46

Technical GuideOperator Interfaces50Programming The MiniLink PDStatusStatus Screen #1 Polling Device System Occupied Venting ModeXXX Min Left

Page 47

Operator Interfaces Technical Guide51Notes:

Page 48

Form: OR-OI-VCM-TGD-01A Printed in the USA November 2005All rights reserved Copyright 2005WattMaster Controls Inc. • 8500 NW Riv

Page 49 - Programming The MiniLink PD

Technical GuideOperator Interfaces6General Programming InformationThe Modular Service Tool or the System Manager allow the user toview any temperatur

Page 50

Operator Interfaces Technical Guide7Mode Selection ButtonsButtonDescriptionModular Service Tool System ManagerSTATUSPressing this buttontakes you dire

Page 51

Technical GuideOperator Interfaces8 InitializingSystem Manager vX.XX Wattmaster Controls Network ModeSystem Manager vX.XX Monday Operations 0

Page 52

Operator Interfaces Technical Guide9System Manager NM & MM Mode Loop SearchWhen the System Manager is configured for Network Mode a loopsearch mus